Remeha Tzerra Ace
Control and adjustment of combustion
Switch on at full load

Press the R and - keys at the same time to select the chimney sweep mode.

The device is now running at low load. wait a moment until L appears in the display.

Press the key twice

The device is now running at full load. Wait a moment until H appears in the display.
Control/set valuesO2 Full load
Tzerra Ace
O2 (%) 3.5 - 4.0
Follow these steps:
- Set the boiler to full load. Measure the percentage of O2. Compare the measured values with those below.
Turn screw A counterclockwise for a lower percentage.

Adjust to full load
See drawing for the position of the adjustment screw A for full load.
Control/set valuesO2 Low load
Tzerra Ace
O2 (%) 4,7 - 5,2
Follow these steps:
- Set the boiler to low load. Measure the percentage of O2. Compare the measured values with those below.
Turn screw B counterclockwise for a lower percentage.

Adjust to Low load
See drawing for the position of the adjustment screw B for Low load.